Application area
-
Continuous monitoring of SF₆ gas density in sealed containers such as GIS, circuit-breakers and load-break switches
-
Suitable for indoor or outdoor installation in substations and switchgear rooms
Features
-
High-precision measurement: range –0.1 MPa to 0.9 MPa; accuracy class 1.0 @ 20 °C, class 1.6/2.5 @ –40 °C – +60 °C
-
Temperature compensation for reliable readings across wide ambient conditions
-
Optional three-way self-sealing valve for leak-free operation
-
RS-485 digital output for integration with SCADA and control systems
-
Rugged construction: IP65 rating; φ100 mm dial; port dimensions M20×1.5 or G1/2 (customizable)
-
Low power consumption: < 20 W host unit
-
Wide operating range: –40 °C – +60 °C, vibration- and shock-resistant design
This meter provides dependable, real-time SF₆ density monitoring to ensure equipment safety and optimal maintenance scheduling.